Display Data Center information:
Floor Layout | |
---|---|
Floor Type | 600mm x 600mm x 400mm(H) nominal raised access floor with anti-static vinyl finish and 7.5kPa floor loading |
Height of floor to ceiling beam | Nominally 3.5m clear from slab to soffit of ceiling beam. |
Power Supply: Power to be delivered at 380 volts, 50 Hz, unless otherwise specified |
|
---|---|
Main supply | 2 incoming supply from 2 different feeder (transformers) back up to each other (1+1 system) |
Emergency Power | General Lighting and Power from 2 generators system (1+1 system) |
UPS | 3kVA per rack from 2 nos. of communal UPS system with 20 mins standby and generator backup (Maximum 250kVA for datacenter 1 & 2) |
AC Distribution | 2 nos. of 18 ways plug-in (one duty and one standby) via Static Transfer Switch (STS) with 32A A/C power supply |
Cable containment system | 1 tier of 300mm(w) wire mesh cabling and 1 tier of fiber guide runner |
Lighting | The lighting at DC is 2x28W T5 fluorescent batten with polycarbonate cover (IP66) and operated via motion sensor. The lighting level is also in a range of 460 – 620 lux. |
Clean Earth | 1 no. of clean earth terminal per row of cabinets |
Air-Con | |
---|---|
Air Conditioning |
|
Fire Protection | |
---|---|
Fire Protection | FM200 system |
Fire alarm | Very Early Smoke Detection Apparatus (VESDA) |
Security | |
---|---|
Security Card Access | Access for entrance door via card readers |
CCTV | 1 nos. of CCTV for all entrances and CCTV viewing from the front & back of racks. |
Building Management System | |
---|---|
BMS | TMs provision will be controlled and monitored by TM only. No interface to tenant |